So that no disaster occurs in hospitals

Fire and man-made safety of medical institutions causes particular concern among the Ministry of Emergency Situations employees. The tragedy that occurred on January 18 in Luhansk, at city hospital No. 7, is still fresh in memory. Then, as a result of the explosion of two oxygen cylinders, 16 people died, and the blast wave demolished four floors of the building – from the second to the fifth.

A month later, the commission revealed the causes of the explosion. Experts’ conclusions: one cylinder contained not pure oxygen, but with impurities of other gases. The container also contained nitrogen and methane. A chemical reaction occurred: a mixture of oxygen with the gas contained in the cylinder reacted with the organic gasket. This led to the ignition of the gasket and a subsequent explosion. It was also found that the second cylinder was damaged by a falling piece of wall. Medical workers of the hospital, who were responsible for safety regulations, are blamed for the tragedy. In addition, untrained people were allowed to work in the intensive care unit.

To prevent disaster in the medical institutions of Odesa, employees of the State Fire Supervision of the Odesa City Department of the Main Directorate of the Ministry of Emergency Situations of Ukraine in Odesa Oblast conducted unscheduled inspections of their fire safety status.

111 healthcare facilities were inspected. Unfortunately, the inspection results are disappointing. Not all heads of medical institutions, according to the legislation, responsible for fire safety, as well as persons responsible for safety regulations, monitor compliance with fire safety standards. Thus, out of 1868 preventive measures previously proposed by the State Fire Supervision of the Ministry of Emergency Situations, 823 have not been implemented. 69 medical facilities require the installation of an automatic fire alarm system (APS). In another 39 facilities, fire alarm signals are not transmitted to the centralized monitoring consoles of the fire department. Fire water supply sources also leave much to be desired. For example, 14 external fire water supply sources need repair, and another one needs to be built. 25 internal fire water supply sources require similar actions. In addition, 38 medical institutions in the city are not fully equipped with primary fire extinguishing means, and in 10 others, evacuation routes do not comply with fire safety regulations.

During the inspections, Ministry of Emergency Situations employees also discovered that 128 sections of the electrical network are operated in violation of the rules for installing electrical networks (PUE).
43 people were brought to administrative responsibility for violating fire safety regulations, and the operation of 10 premises was prohibited. In addition, Ministry of Emergency Situations employees conducted 111 fire safety briefings.

The largest number of violations was found during the inspection of maternity hospital No. 7 (11 Kosmonavtov St.). In particular, fire-retardant treatment of wooden structures in the attic has not been carried out, there are fixed metal grilles on the windows, and the APS system is faulty. One of the basement rooms is used as a workshop. There is combustible sheathing – plastic – on the walls of the central staircase on the evacuation routes. The design documentation for the premises built for the diesel power plant has not been coordinated with the state fire supervision authorities. Officials of the institution have not undergone special training. To avoid an emergency at this facility, employees of the State Fire Supervision of the Ministry of Emergency Situations were forced to issue two orders on the application of preventive measures. And for violating fire safety regulations, two officials were brought to administrative responsibility.

The requirements of fire safety are also treated carelessly at city hospital No. 10 (61 Malinovskogo St.). For example, the distance from the oxygen station to the inpatient building is reduced. In the station room, electric lighting lamps are not protected by solid glass shades. The premises of the medical institution are not equipped with APS, and fire hydrants are not equipped with hoses and nozzles. Fire extinguishers have not been recharged, there are insufficient primary fire extinguishing means, and the insulation resistance has not been measured. For violating fire safety regulations, an official was brought to administrative responsibility.

Significant violations were also identified at LLC “Medical Center “INTO-SANA” at 2 Varnenskaya St. In particular, a utility room in the treatment building was adapted as a storage for oxygen cylinders. Also, the automatic fire alarm system has not been serviced, and the signal from the APS is not transmitted to the round-the-clock monitoring console of the fire department. The fire shield on the territory of the medical institution is not fully equipped. To prevent an emergency, employees of the State Fire Supervision of the Ministry of Emergency Situations temporarily prohibited the operation of the utility room where the cylinders are stored until the deficiencies are rectified, and issued an order on the application of preventive measures.

However, there are also heads of medical institutions in Odesa who care about people’s safety not in words, but in deeds. Maternity hospital No. 2 (24 Staroportofrankovskaya St.) can serve as an example. In particular, the premises here are equipped with APS, and it is connected to the central console of the round-the-clock fire department monitoring. The building is fully equipped with primary fire extinguishing means, and all fire extinguishers are certified. Insulation resistance measurements have been carried out everywhere. All staff of the maternity hospital have been briefed. Ministry of Emergency Situations employees also conducted fire safety briefings.

Children’s polyclinic No. 6 at 32a Glushko Ave. also conscientiously cares about compliance with fire safety standards. The building is equipped with APS, and the internal fire water supply system is in good working order. Evacuation routes comply with fire safety standards. The premises of the medical institution are fully equipped with primary fire extinguishing means. Fire safety briefings have been conducted with its staff.

The heads of these institutions understand that one cannot save money on people’s safety. It is much easier to prevent an emergency than to eliminate its tragic consequences. Medical institutions need to allocate additional funds to ensure the fire safety of facilities: preventing emergencies concerns not only rescuers. If a disaster occurs, you need to call “101” immediately. Ministry of Emergency Situations rescuers are always ready to be the first to help!